Home Company Info Product List Contact Details
Homeproduct Directory

Nuclear Power Station with cable High-Temperature Resistant and Radiation Resistant Magnet Wire

Nuclear Power Station with cable High-Temperature Resistant and Radiation Resistant Magnet Wire
company Shanghai Special Cable Electrotechnical Co., Ltd
Categories Cable Sleeves
Update2011-03-31
Original RegionChina
Nuclear Power Station with cable High-Temperature Resistant and Radiation Resistant Magnet Wire

The magnet wire is applicable to all electromagnetic winding wires used in nuclear power equipment with temperature index of 260and 350℃, and can meet requirements of high temperature and radiation in nuclear power equipment or other special conditions.

StandardQ/SC-HD-004-2008

Main properties:
Operating temperature:-25℃~+260℃(350℃)
Relative humidity:8550℃)
Performance of Irradiationintegral neutron flux 1×1014 n/cm2
-ray absorbed dose1×107Gy

Type, Name and Size

type

name

Specifications

THW260

High temperature resistant and radiation resistant magnet wire, temperature index 260

0.20~4.0mm

THW350

High temperature resistant and radiation resistant magnet wire, temperature index 350

0.20~5.0mm

Main technical parameters:
1.The magnet wire can meet the requirements of high temperature and radiation in nuclear power equipment or other special conditions.
2.Performances of DC. Resistance, thickness of insulation, elongation at break, cohesive strength and breakdown voltage all comply with technique criterion of our company.
3.Performance of magnet wire(350℃):
1)Maintained breakdown voltage above 2000V under 450heat aging test for 1200 hours.
2)Insulation resistance test at high temperature: insulation resistance is 108 m at 500 ℃
3)450aging heating insulation resistance test: insulation resistance is 108 m at 450for 1000 hours.
4)Thermodynamic life simulation test: extrapolation temperature: 410 ℃

The 260℃high temperature resistant and radiation resistant magnet wire has been used in C1 project of Chashma nuclear power plant in Pakistan. Pakistan C1 project is always safe since putting into operation in 1998.

Nuclear Power Station with cable High-Temperature Resistant and Radiation Resistant Magnet Wire on sale

Products Showcase

See more products from this supplier.

Do you want to show products of your own company? Join FREE now!